Hello! Main Products: Anticorrosive Materials, Heat Preservation Materials, Waterproof Materials, etc

power cable

hotsearch
14138755579359.jpg
  • 14138755579359.jpg

Flame retardant crosslinked power cables

cpfl:
This product is manufactured in accordance with GB1270 "plastic insulated power cable with copp…
Description

1kV-35kV flame retardant crosslinked polyethylene insulated power cable

Product standard:

This product is manufactured in accordance with GB1270 "plastic insulated power cable with copper and aluminum core rated voltage 35kV and below", and can be manufactured in accordance with IEC, British standard, German standard and American standard as recommended by the international electrotechnical commission.

Cable type:
ZR - YJVZR - YJLVZR - YJYZR - YJLY
ZR - YJV22ZR - YJLV22ZR - YJV23ZR - YJLV23
ZR - YJV23ZR - YJLV23ZR - YJV33ZR - YJLV32
ZR - YJLV33


Scope of application: this product is suitable for power distribution line distribution with rated power frequency voltage 3.6/ kv-26/35kv. Service characteristics: the rated power frequency voltage Uo/U is 3.6/6kv-26/35kv. ● the allowable long - term high operating temperature of the cable conductor is 90℃. ● in the case of short circuit (* long duration not exceeding 5s) the * high temperature of the cable conductor shall not exceed 250℃. ● the ambient temperature during cable laying shall not be lower than 0℃. Cable bending radius: three-core cable shall not be less than 15 times of the outer diameter of the cable; A single-core cable shall not be less than 20 times the outer diameter of the cable.

Selection of cable rated voltage

● the rated voltage of the cable shall be suitable for the operating condition of the cable system, expressed as Uo/U (Um) KV. Uo-- rated power frequency voltage between conductors for cable design to ground or metal shielding; U-- rated power frequency voltage between conductors for cable design; Um-- the * large value of "* high system voltage" that the device can withstand.

The Uo values of cables for three-phase systems are recommended as follows:


kv
Um 
kv
Uo * kv
Class A and B systems
C class system
6
7.2
3.6
6
10
12
6
8.7
15
17.5
8.7
12
20
24
12
18
30
36
18
-
35
40.5
21
26

Class A system -- any phase conductor of this system can be separated from the system within 1min when it comes into contact with the ground or ground conductor; Class B systems - this type of system * includes conditions for short-running of single-phase ground fault which shall not exceed 1h, but in any case, *** shall not exceed 8h and the total duration of ground fault shall not exceed 125h per year; Class C systems - systems that do not belong to class A or class B.


Browse:
On A:Crosslinked power cables
Next:No
Return To The Top

分享到: